| Brand name, Manufacturer name, Manufacturer | SQUARE D |
| DimensionUnit | mm |
| Extra Product Name | PowerLogic EM3500 DIN rail meter - BACnet - flexible transducer | Mayer Electric |
| UPC, MPN, SKU | SQDMETSEEM3560A |
| color, Color | dark grey |
| depth, length | 59.0 |
| height | 91.0 |
| height_Attrib | Height |
| jsonUrlData | /Product/SQUARE-D-PowerLogic-EM3500-DIN-rail-meter-BACnet-flexible-transducer-SQDMETSEEM3560A |
| jsonUrlData2 | 954364fc-1388-41ac-89c2-aeea00567ba4 |
| length_Attrib | Depth |
| moq, multiple, tierMinQty1 | 1 |
| qtyInStock | 0 |
| tierPrice1 | 0.0 |
| width | 107.0 |
| width_Attrib | Width |
| Product Or Component Type | energy meter |
| Product Name | PowerLogic EM3500 |
| Device Short Name | EM3560A |
| Metering Type | peak demand power PM, QM, SM || current I1, I2, I3, Iavg || demand power P, Q, S || voltage U21, U32, U13, V1, V2, V3 |
| Range | PowerLogic |
| Network Frequency | 50 Hz || 60 Hz |
| Information Displayed | status and alert || communication with system || input/output status || error || Tx activity || Rx activity || instant power per usage |
| Communication Port Support | screw terminal block RS485 |
| Function Available | external synchronisation to communication || fixed or rolling block |
| [Ue] Rated Operational Voltage | 90...347 V AC 50/60 Hz between phase and neutral UL || 156...600 V AC 50/60 Hz between phases UL || 90...300 V AC 50/60 Hz between phase and neutral CE || 125...300 V DC |
| Mounting Mode | by screws || clip-on |
| Local Signalling | Red LED threshold reached || Green flashing LED output signal |
| Power Consumption In W | 3 W 300-300 V |
| Measurement Accuracy | power +/- 0.5 % || energy +/- 0.5 % |
| Standards | IEC 61010-1 || UL 508 || CSA C22.2 No 14-05 |
| Technology Type | electronic |
| Number Of Outputs | 1 alarm output |
| Mounting Support | DIN rail |
| Power Consumption In Va | 5-5 VA 347 V AC between phase and neutral) || 5-5 VA 600 V AC between phases) |
| Buffer Size | 32-bit 3 |
| Product Certifications | CE IEC 61010 || cULus UL 508 |
| Poles Description | 3P + N |
| Communication Port Protocol | BACnet MS/TP 9600 bauds...115200 bauds (automatic detection) - 2-wire |
| Communication Service | total cumulated energy || total cumulated active energy |
| Data Recording | energy consumption logs |
| Ride-Through Time | 100 ms 120 V AC |
| Analogue Input Type | Rogowski coil 50...5000 A |
| Display Type | Backlit LCD |
| Display Digits | 5 |
| Number Of Inputs | 1 pulse |
| Device Application | sub billing || partial meter |
| Tamperproof Of Settings | protected by access code |
| Accuracy Class | class 0.5S power IEC 62053-22 || class 0.5S energy IEC 62053-22 || class 0.5S power ANSI C12.20 || class 0.5S energy ANSI C12.20 |
| Measurement Current | 20-5000 A |
| Rated Voltage | 90-347 V |
| China Rohs Regulation | Product out of China RoHS scope. Substance declaration for your information. |
| Rohs Exemption Information, Mercury Free | Yes |
| Eu Rohs Directive | Compliant |
| Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
| California Proposition 65 : WARNING: This product can expose you to chemicals including | Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
| Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
| Ambient Air Temperature For Operation | -30-70 ?C |
| Height | 91 mm |
| Ambient Air Temperature For Storage | -40-85 ?C |
| Relative Humidity | 0-95 % |
| 9 Mm Pitches | 12 |
| Width | 107 mm |
| Depth | 59 mm |