| Brand name, Manufacturer name, Manufacturer | SQUARE D |
| DimensionUnit | mm |
| Extra Product Name | PowerLogic EM3500 DIN rail meter - pulse - current transformer | Mayer Electric |
| UPC, MPN, SKU | SQDMETSEEM3502 |
| color, Color | dark grey |
| depth, length | 59.0 |
| height | 91.0 |
| height_Attrib | Height |
| jsonUrlData | /Product/SQUARE-D-PowerLogic-EM3500-DIN-rail-meter-pulse-current-transformer-SQDMETSEEM3502 |
| jsonUrlData2 | a22c20dc-ee5b-4cec-a373-aeea00567b8d |
| length_Attrib | Depth |
| moq, multiple, tierMinQty1 | 1 |
| qtyInStock | 0 |
| tierPrice1 | 0.0 |
| width | 107.0 |
| width_Attrib | Width |
| Product Or Component Type | energy meter |
| Product Name | PowerLogic EM3500 |
| Range | PowerLogic |
| Device Short Name | EM3502 |
| Metering Type | demand power P, Q, S || peak demand power PM, QM, SM || current I1, I2, I3, Iavg || voltage U21, U32, U13, V1, V2, V3 |
| Network Frequency | 60 Hz || 50 Hz |
| [Ue] Rated Operational Voltage | 90...347 V AC 50/60 Hz between phase and neutral UL || 156...600 V AC 50/60 Hz between phases UL || 90...300 V AC 50/60 Hz between phase and neutral CE || 125...300 V DC |
| Output Voltage | 30 V AC/DC |
| Standards | UL 508 || CSA C22.2 No 14-05 || IEC 61010-1 |
| Number Of Outputs | 2 pulse || 1 alarm output |
| Mounting Support | DIN rail |
| Power Consumption In Va | 5-5 VA 347 V AC between phase and neutral) || 5-5 VA 600 V AC between phases) |
| Product Certifications | CE IEC 61010 || cULus UL 508 |
| Communication Service | total cumulated active energy || total cumulated energy |
| Ride-Through Time | 100 ms 120 V AC |
| Display Digits | 5 |
| Tamperproof Of Settings | protected by access code |
| Measurement Current | 5-32000 A |
| Information Displayed | status and alert || communication with system || input/output status || error || Tx activity || Rx activity || instant power per usage |
| Function Available | fixed or rolling block |
| Mounting Mode | clip-on || by screws |
| Local Signalling | Red LED threshold reached || Green flashing LED output signal |
| Power Consumption In W | 3 W 300-300 V |
| Measurement Accuracy | power +/- 0.2 % || energy +/- 0.2 % |
| Technology Type | electronic |
| Poles Description | 3P + N |
| Data Recording | energy consumption logs |
| Analogue Input Type | split core current transducer 0.333 V or 1 V |
| Display Type | Backlit LCD |
| Device Application | partial meter || sub billing |
| Accuracy Class | class 0.2S power IEC 62053-22 || class 0.2S energy IEC 62053-22 || class 0.2S power ANSI C12.20 || class 0.2S energy ANSI C12.20 |
| Rated Voltage | 90-347 V |
| Rohs Exemption Information, Mercury Free | Yes |
| Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
| California Proposition 65 : WARNING: This product can expose you to chemicals including | Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
| Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
| China Rohs Regulation | X |
| Eu Rohs Directive | Compliant |
| Ambient Air Temperature For Operation | -30-70 ?C |
| Height | 91 mm |
| 9 Mm Pitches | 12 |
| Ambient Air Temperature For Storage | -40-85 ?C |
| Relative Humidity | 0-95 % |
| Width | 107 mm |
| Depth | 59 mm |